Fire Extinguisher Quantity Calculator
Work out how many fire extinguishers your premises needs, and which types, from floor area and risk factors, per BS 5306-8 guidance.
Calculator Inputs
Extinguisher Type Breakdown
| Type | Rule Applied | Count |
|---|---|---|
| Class A (water/foam) | - | - |
Scenario Analysis
| Scenario | Total Required | Shortfall/Surplus |
|---|---|---|
| Current setup | - | - |
Is There A Legal Number Of Fire Extinguishers You Must Have?
Not a single fixed figure. The Regulatory Reform (Fire Safety) Order 2005 requires the "responsible person" for a non-domestic premises in England and Wales to provide "appropriate fire-fighting equipment," but leaves the exact number, type and siting to be determined by a suitable and sufficient fire risk assessment. In practice, BS 5306-8 - the British Standard covering selection and installation of portable fire extinguishers - is the technical guidance most assessments, suppliers and this calculator use to translate "appropriate" into an actual number.
The 200 m² Rule And The 2-Per-Floor Minimum
BS 5306-8 guidance treats one 13A-rated Class A extinguisher as covering roughly 200 m² of ordinary combustible risk (paper, wood, textiles), with a minimum of 2 Class A extinguishers on every floor regardless of size - so a 50 m² shop unit and a 199 m² shop unit both need exactly 2, while a 450 m² office needs 3 (ceil(450/200) = 3). The same guidance sets a maximum 30-metre travel distance to reach a Class A extinguisher, meaning units generally need siting no more than about 60 metres apart - a count that's technically correct on paper can still fail this rule if extinguishers are clustered near one door instead of spread across the floor.
Why Extinguisher Type Matters As Much As Count
A Class A water or foam extinguisher is not safe to use on a live electrical fire or a deep-fat fryer fire - using the wrong type can make either worse. CO2 extinguishers are the standard choice near electrical equipment and server rooms because they leave no residue and don't conduct electricity back through the extinguisher; wet chemical (Class F) extinguishers, paired with a fire blanket, are the standard for commercial kitchens with deep-fat frying, because they cool and seal burning oil rather than spreading it. Premises storing flammable liquids typically need foam extinguishers in addition to general Class A coverage, since water alone can spread a burning liquid rather than extinguish it.
Common Mistakes When Estimating Extinguisher Numbers
The most common mistake is applying the 200 m² rule and stopping there, forgetting the 2-per-floor minimum - a small 80 m² unit still needs 2, not 1, under this guidance. The second is treating all extinguishers as interchangeable: a premises with 8 Class A extinguishers and a server room with no CO2 unit nearby has the wrong type mix even if the total count looks generous. The third is applying one floor's area across a multi-floor building where floor sizes actually differ significantly - a 3-floor building with a 600 m² ground floor and two 150 m² upper floors needs the calculation run separately per floor, not once using an average.
What Happens Next?
Once you have an indicative count and type mix from this calculator, the next step is commissioning (or reviewing) a formal fire risk assessment from a competent person, who will check your specific building layout, occupancy numbers and hazards against this estimate - and confirm exact siting so no one has to travel more than the 30-metre guideline to reach a Class A extinguisher. If your current stock is well short of the indicative total, prioritise the highest-risk gaps first (an electrical risk area with no CO2 extinguisher, or a kitchen with no wet chemical unit) rather than simply adding more of whatever type you already have.
Method And Limits
This tool applies BS 5306-8's widely used technical guidance for portable fire extinguisher provision, checked 2026-08-11: one 13A-rated Class A extinguisher per 200 m² of floor area, a minimum of 2 Class A extinguishers per floor regardless of size, and a maximum 30-metre travel distance to reach a Class A extinguisher. CO2, foam and wet chemical provision follow simpler 1-per-floor or 1-per-kitchen rules of thumb common in UK fire-safety supplier guidance, rather than their own coverage-area formulas.
- Does not replace a fire risk assessment. The Regulatory Reform (Fire Safety) Order 2005 requires "appropriate fire-fighting equipment" but does not itself specify numbers or types - those are legally determined by a suitable and sufficient fire risk assessment carried out by a competent person. Treat this tool's output as a starting estimate to sanity-check that assessment, not a substitute for it.
- Does not check travel distance or siting geometry. It calculates a total count from floor area, but does not verify that extinguishers can actually be positioned so no one travels more than 30 metres to reach one - an oddly shaped or subdivided floor plan may need more extinguishers than the area-only figure suggests.
- Does not model every risk type. It covers the four most common UK premises risks (general Class A, electrical, flammable liquids, kitchen frying) but not others a full risk assessment would consider - gas cylinders, specific chemical hazards, or high-value electronic equipment needing a clean-agent extinguisher, for example.
- Assumes uniform floor area across all floors entered. A premises with a large ground floor and small upper floors will get an inaccurate per-floor split if you enter an averaged area; run the tool per distinct floor size instead.
Figures checked .
Frequently Asked Questions
Is there a legal minimum number of fire extinguishers in the UK?
Not a fixed number. The Regulatory Reform (Fire Safety) Order 2005 requires "appropriate fire-fighting equipment" for non-domestic premises in England and Wales, but the exact number, type and siting must be determined by a fire risk assessment, not a single legal figure. BS 5306-8's guidance - one 13A Class A extinguisher per 200 m², minimum 2 per floor - is the widely used technical benchmark most assessments and suppliers work from, which is what this calculator applies.
Where does the "one per 200 m²" figure come from?
BS 5306-8, "Selection and installation of portable fire extinguishers", the British Standard most UK fire-safety guidance and suppliers cite for extinguisher provision. A 13A-rated water or foam extinguisher is judged able to cover roughly 200 m² of ordinary Class A combustible risk (paper, wood, textiles, general office and retail materials).
Why is there a minimum of 2 extinguishers per floor even for a small room?
BS 5306-8 guidance sets a 2-per-floor minimum regardless of area, so a single small office or shop unit still needs 2, not 1 - partly for redundancy (a spent or faulty extinguisher shouldn't leave a floor with none) and partly so a fire in one part of a small floor doesn't leave someone needing to cross the fire to reach the only extinguisher.
What is a CO2 extinguisher for and why does electrical risk add one?
CO2 (carbon dioxide) extinguishers are the standard choice for fires involving live electrical equipment, because they leave no residue and don't conduct electricity back through the extinguisher onto the user - unlike water or foam extinguishers, which are not safe to use on live electrics. If your premises has server equipment, electrical panels or similar risk, guidance typically adds at least one CO2 extinguisher per floor alongside the Class A provision.
What extinguisher does a commercial kitchen need?
A wet chemical (Class F) extinguisher, designed for cooking oil and fat fires, plus a fire blanket for smaller pan fires - a standard water, foam or CO2 extinguisher is not appropriate for a deep-fat fryer fire and can make it worse. This calculator adds one of each when you flag a commercial kitchen with deep-fat frying.
My premises has multiple kitchens - does the calculator handle that?
Not automatically - it adds one wet chemical extinguisher and one fire blanket regardless of floor count, assuming a single kitchen area. If you have more than one separate kitchen, add one more wet chemical extinguisher and one more fire blanket per additional kitchen to the tool's total by hand.
Does a bigger floor area always mean more extinguishers?
Only above the 200 m² threshold per extinguisher, and only once you cross into needing a 3rd, 4th (and so on) unit - the minimum of 2 per floor means a 50 m² room and a 199 m² room both need exactly 2 Class A extinguishers under this guidance; the count only increases once a floor passes 200 m², 400 m², 600 m² and so on.
What if I already have more extinguishers than the calculator says I need?
That's a common and reasonable outcome, especially in premises that have grown or changed use over time - the tool shows this as a surplus rather than treating it as wrong. Extra Class A coverage is rarely a problem, but if your surplus is concentrated in the wrong type it's still worth checking the mix against your risk assessment, not just the total count.
Does this calculator account for the type of extinguisher already on site?
No - the "extinguishers you currently have" field is a single total count compared against the total requirement, not broken down by type. If your current stock is mostly one type and light on another, the total comparison alone can hide a type-specific shortfall - check the breakdown table's type-by-type figures against what you actually hold, not just the overall total.
How often do fire extinguishers need to be serviced or replaced?
This calculator doesn't cover servicing schedules, but UK guidance generally recommends an annual service by a competent person (often BAFE-registered), alongside monthly visual checks by premises staff for damage, tampering or a low pressure gauge reading. Extinguishers are typically replaced or recharged after use, and stored-pressure water and foam types are commonly discharge-tested and refilled around every 5 years per manufacturer guidance.
Is this the same as a fire alarm or smoke detector requirement?
No - fire extinguishers are firefighting equipment for tackling a small fire at its early stage; fire detection and alarm systems are a separate requirement under the same Fire Safety Order, sized differently (by building layout and evacuation strategy, not floor area per extinguisher). This calculator only covers portable extinguisher provision.
Who is legally responsible for getting this right?
The "responsible person" for the premises - typically the employer, building owner, or whoever has control of the premises - under the Regulatory Reform (Fire Safety) Order 2005. That person must ensure a suitable and sufficient fire risk assessment is carried out and kept up to date, which this calculator can inform but not replace.
Can I use this for a residential building I manage?
This tool is built for non-domestic premises risk (offices, shops, warehouses) covered by the Fire Safety Order. Blocks of flats and other residential buildings sit under different, more specific fire safety guidance, so use guidance specific to residential buildings instead of this tool's figures for that use case.
Sources
- BS 5306-8 guidance summary
- gov.uk fire safety risk assessment guides
- gov.uk - Fire safety in the workplace: who's responsible
Last updated: 2026-08-11. This page gives an indicative planning estimate only and is not a fire risk assessment.